# IEQ 3.5 Thermal Comfort - Ceiling Fans - Non-Residential

# Applies to

All non-residential development

# Objective

To provide comfortable indoor spaces and reduce energy needed for heating and cooling.

# Summary

Points are awarded where a minimum of 50% of regular use areas in tenancies are serviced by ceiling fans.

Additional points are awarded where a higher proportion of the regular use areas are serviced by ceiling fans.

Maximum points are awarded when 100% of the regular use areas are serviced by ceiling fans.

Ceiling fans are to permanently installed and have a speed controller. The floor area served by a ceiling fan is to be the lessor of:

  • Manufacturer's recommendations
  • 15sqm for a blade rotation diameter 900mm or greater but less than 1200mm
  • 25sqm for a blade rotation diameter of 1200mm or greater

# Documentation & evidence required

Floor plans showing areas serviced by ceiling fans.